Switch Amplifier KCD2-SOT-Ex2
Key Benefits at a Glance
2-channel isolated barrier
24 V DC supply (Power Rail)
Dry contact or NAMUR inputs
2 passive transistor outputs
Reversible mode of operation
Line fault detection (LFD)
Housing width 12.5 mm
Up to SIL 2 (SC 3) acc. to IEC/EN 61508
Supply
Connection Power Rail or terminals 9+, 10-
Rated voltage Ur 19 ... 30 V DC
Ripple ≤ 10 %
Rated current Ir 30 ... 20 mA
Power dissipation≤ 800 mW including maximum power dissipation in the output