IMX12-TI02-1TCURTDR-1I1R-CPR/24VDC/CC Temperature Measurement Amplifier TURCK
General Information
The single-channel temperature measuring amplifier IMX12
TI02-1TCURTDR-1I1R-CPR/24VDC/CC has inputs for: thermocouples according to IEC 60584, DIN 43710,
GOST R 8.585-2001, low voltage (-150 …+150mV), RTD according to IEC 60751, DIN 43760, GOST
6651-94 (2-, 3- and 4-wire) and resistors 0…5 kò (2-, 3- and 4-wire).
The device can be powered via a power bridge, which can also transmit a collective fault signal.
The cold junction compensation can be set to an external value, an internal value or a constant value.
The device is configured via the PC interface. The current output can be set to 0/4 …
20mA source or sink. The device has an additional reversible switching
relay output for monitoring overvoltage or undervoltage or window function limit values.
The green LED indicates that the product is operating normally.
Input circuit faults cause the red indicator to flash, according to NE44, the internal
error red readable indicator is stable. The fault current can be adjusted <
3.5 mA or > 21.5 mA.
Edition • 2025-02-28T18:43:01+01:00
■ Open/short circuit monitoring of input circuits
The device can be used (according to high and low requirements of IEC61508) in safety circuits up to SIL2 and meets the requirements of NE21.
Equipped with removable cage clamp terminals.
The device can be used in safety circuits with SIL 2 certification (high/low level safety requirements in accordance with IEC 61508) (hardware
fault tolerance HFT = 0).
The device is equipped with removable spring clamp terminals.
■ Parameter setting via PC
■ Intrinsically safe output circuits
■ Plug-in cage clamp terminals
■ Power bridge (connector included in delivery)
■ ATEX, IECEx, cFM, cUL, NEPSI, INMETRO, Kosha, TS
■ Usage in hazardous area zone 2
■ SIL
Technical Parameters:
Model: IMX12-TI02-1TCURTDR-1I1R-CPR/24VDC/CC
Article No. 7580506
Operating voltage 24 VDC
Operating voltage UB
10…30 VDC
Power consumption ð 2 W
Typical power loss ð 1.6 W
Input circuit RTD type DIN EN 60751 Pt50, Pt100, Pt 500, Pt1000
RTD type DIN EN 43760 Ni50, Ni100, Ni500, Ni1000
RTD type Gost 6651-94 Pt50, Pt100, Pt 500, Pt1000,
CU50, Cu53, Cu100, CU500, CuZn100
TC type DIN EN 60584 Type A, Type B, Type C, Type E, Type J, Type K
Type, Type N, Type R, Type S, Type T
Type TC DIN 43710 Type L
Type TC Gost 8.585-2001 Type A1, Type A2, Type A3, Type L, Type M
Low voltage input -150…150 mV
Input resistance 0…5000 ò
Thermocouple -50…200°C; 0…400°C; 0…600°C
HONGKONG XIEYUAN TECH CO., LIMITED